Entrust test(94)-187A

Moving-thermostable test enregister

List 2

Date of test:July 9th 1994 number of poles:3 test frequency(Hz):50

Test No.II2-572

Numbershowing-
thepicture

Test content

pole

peak value endurable voltage (kA,peaks)

Endure electrical current at a short time(kA)

short circuit time last(kA)

Situation of the tested

 

 

Stable

 

 

 

 

 

 

 

Stable

 

 

 

 

 

 

 

Stable

 

 

 

 

 

-01

940953

Moving-thermostable

A

77.5

32.9

4.1

Not craze or melt

B

43.5

31.4

C

80.3

33.5

 

Entrust test(94)-187B

Temperature rise test report

Tested type

NHBT

Num.

Test current

1000A

Number of poles:3

Frequency of electric current:50Hz

Meeting point pressure

A:B: C: N

Wind speedŁ:weaker than0.15m/s

Connect bus bar

Cuprum bus bar, x mm x mm ,head length(m): tail length(m):

Data of temperature rise(k)

Number of tested part

Naked bus bar temperature rise(environmental temperature27.4oC)

Temperature rise with the insulate sleeve( environmental temperature28.3oC)

Permitted temperaturerise(k)

indication

A

B

C

A

B

C

1

32.2

 

 

25.0

 

 

50

 

2

48.1

 

 

29.7

 

 

70

 

3

34.6

 

 

30.3

 

 

50

 

4

 

36.4

 

 

29.6

 

50

 

5

 

49.8

 

 

32.2

 

70

 

6

 

33.7

 

 

29.3

 

50

 

7

 

 

35.5

 

 

25.2

50

 

8

 

 

55.6

 

 

29.2

70

 

9

 

 

35.2

 

 

27.5

50

 

Test result

Up to grade

date

 

 

 

 

July of 1994

 

Entrust test(94)-187C

 

1: Purpose of the test:See the insulate performances of NHBT when shrink on the 10kv bus bar.
2: Way of test:Put NHBT on rectangular bus bar(80xx8x1200mm) and shrink it. The average thickness is2.3mm. Do the experiment when the distance between poles is 100mm, 90mm and 85m. Take the average value of 3times according to GB<solid insulate material test>.
3:test result:

Distance between poles(mm)

One minute industry frequency test

Endure test of whole wave thunder strike

Positive

cathode

Given voltage
(kv)

Voltag
- e
times

break-downti-mes

Given voltage(kv)

Voltage
times

break-downtim
es

Given voltage
(kv)

Voltage
times

Breakd
owntimes

100

42

1

0

75

15

0

75

15

0

90

42

1

0

75

15

0

75

15

0

85

42

1

0

75

15

0

75

15

0

Take the average of 3times of the test, it is 21.4kV/mm

P=96.3k       Pa tdry=24.5oC          twet=22oC

 

Lab of Xi'an high voltage electric implement graduate school

Test report

No.00426

 

Page 5

 

Endure test of high voltage switch implement(working frequency)

 

Date of test:09 - 18-2000

 

Distance between tested

Voltage part

1 min working frequency voltage endure

 

Dry

article(mm)

 

voltage ( KV)

Voltage times

break-down times

 

290

A-B

95.0

1

0

 

280

A-B

95.0

1

0

 

270

A-B

95.0

1

0

 

260

A-B

95.0

1

0

 

250

A-B

95.0

1

0

 

Atmosphere of tested area

P=96.6kPa tdry=25.0oC twet=22.0oC
Atmosphere revise submultiple Kt=1.01